M-System M2D Mini-M Series Super-Mini Signal Conditioners; Current Loop Supply (non-isolated) Simple Type: Signal Conditioning

Signal conditioners convert a field signal from various sensors into standard signal suitable for processing in PLC, DCS or PC-based systems. They are also used to boost a signal to increase load drive capability, to isolate a signal to stop ground loops. More than 75000 combinations of process signal I/O, power input and mounting configuration are selectable. Additionally, M-System offers the broadest line of signal splitters available. M2 Series Signal Conditioners are designed to accept a largest range of process signal inputs and provide a standard and non-standard DC output.

Download the datasheet (PDF)

For Resellers and High Volume Orders:
Please request a quote to obtain preferred pricing.

Features

  • 2000V AC isolation
  • Base socket included with modules
  • CE marking and UL/C-UL Class 1 Div 2 approval (selected models)
  • Fixed range or PC programmable models selectable
  • M2 use a compact-size, plug-in socket base for quick installation or replacement of modules without disturbing wiring.
  • Selectable 100-240V AC/24V DC power input
  • Standard DIN rail or surface mounting

Specifications

    General
  • Accuracy: ±0.1 % (accuracy of the receiving resistor): Performance
  • Connection: M3 screw terminals (torque 0.8 N·m)
  • Construction: Plug-in
  • Current limited: 35 mA max.
  • Current rating: = 22 mA DC
  • Dielectric strength: 2000 V AC @1 minute: Performance
  • Housing material: Flame-resistant resin (black)
  • Insulation resistance: = 100 MO with 500 V DC: Performance
  • Isolation: Input or output to power
  • Line voltage effect to supply output: ±3 % over voltage range: Performance
  • Output voltage: 24 – 28 V DC with no load
  • Protected time duration: No limit
  • Temp. coefficient: ±0.003 %/°C (±0.002 %/°F): Performance

 